The purpose of a Reduced Pressure Detector Fire Protection Backflow Prevention Assembly is to keep contaminated water from fire protection systems from flowing back into a potable water distribution system when some abnormality in the system causes the pressure to be temporarily higher in the contaminated part of the system than in the potable water supply piping. These assemblies are designed to detect low rates of flow up to 2.0 GPM (.126 L/s) caused by leakage or unauthorized use. The RPDA & RPDA-II assemblies consist of two independently-acting check valves, internally force loaded to a normally closed position & separated by an intermediate chamber (or zone) in which there is a hydraulically operated relief means for venting to atmosphere, internally force loaded to a normally open position. These assemblies are designed to operate under continuous pressure conditions. The assembly shall include two properly located, tightly closing shut-off valves & properly located test cocks. If you choose "Download" as your Delivery Method, you will be able to download this product by going to the Customer Service, Downloads page after you have checked out. Products downloaded are not to be reproduced or distributed in any way.
|
|||||||||||||
|